Description
The TITANEX® flexible rubber cable range offers exceptional performances and is designed to release you from all your constraints. Robust yet flexible, TITANEX® is easy to use and withstands the toughest of conditions, such as hard-wearing situations, extreme temperatures and most chemicals. For more than 50 years the TITANEX® cable range properties have been recognized as the best choice for all mobile and fixed installations in industrial environments such as construction sites, cranes, machines tools, factories, generators etc.
TITANEX® is also suitable for public environments and temporary events such as festivals or sports competitions, where the cable is often laid directly on the ground with no protection.
The cable may be rated 0,6/1 kV where the installation has built-in protection and for motors in lifting appliances – machine tools – etc.
Standards
International: EN 50525-2-21; HD 22.4; HD 516; IEC 60245-4 type 66
National: NF C 32-102-4
Declaration of Performance: Reaction to fire: Eca according to EN50575:2014+A1:2016
Installation
This cable can be installed in open air or be buried but with extra mechanical protection.
Conductors laid up
Assembled conductors.
Construction Characteristics
Conductor material | Bare copper |
Conductor flexibility | Flexible class 5 |
Insulation | Special cross-linked elastomer |
Outer sheath | Special cross-linked elastomer |
Sheath colour | Black |
Lead free | Yes |
With Green/Yellow core | No |
With smaller neutral conductor | No |
Dimensional Characteristics
Number of cores | 2 |
Conductor cross-section | 1.5mm² |
Minimum outer diameter | 8.5mm |
Maximum outer diameter | 11.0mm |
Approximate weight | 111kg/km |
Electrical Characteristics
Rated Voltage Uo/U (Um) | 450 / 750 V |
Permissible current rating in open air | 26A |
Voltage drop, single phase | 27.0V/A.km |
Mechanical Characteristics
Mechanical resistance to impacts | AG3 |
Cable flexibility | Flexible |
Usage Characteristics
Silicone free | Yes |
Chemical resistance | Accidental |
Water proof | Good |
Flame retardant | C2, NF C 32-070 & IEC 60332-1 |
Packaging | Cut to length |
Operating temperature, range | -25 .. 55°C |
Minimum static operating bending radius | 33mm |
Minimum dynamic operating bending radius | 66.0mm |
Max. conductor temperature in service | 90°C |
Short-circuit max. conductor temperature | 250°C |
Oil resistance | Yes |
RoHS compliant | Yes |